| ZGS9-10 model (American model)
combinated transformer: |
| |
 |
¡¡ |
| characteristics of products: |
| |
| small dimension, compact structure: about one third
of the combined transformer substation of the same volume; whole insulation,
whole airproof structure; needless of insulation distance, guaranteeing
personal safety; holding characteristics of insulating switch: high
voltage wire adopts cable tie-in, able to operate 200A current; complete
protection; adopts double-fuse (plug-in fuse and in support protective
fuse) protection, plug-in fusing thread holds double-agility; adopts
¡÷/Yo tieing method and three-phase & five-column structure: high
quality of voltage, neutral point no drifting, heatless transformer
body, low noise, good thunder resistance capability; both used in
ring net and teminal with convenient conversion; strong overloading
capability: 2 hours for allowable overloading 2 times, 7 hours for
overloading 1.6 times; defending grade is IP33: the transformer body
adopts advanced antisepsis technology, used in various abominable
environment. |
sequence number |
items |
parameters |
1 |
rated voltage£¨kV£© |
10/0.4 |
2 |
rated frequency£¨Hz£© |
50 |
3 |
rated volume£¨kVA£© |
100,125,160,200,250,315,400,
500,630,800,1000,1250,1600 |
4 |
working frequency compression resistance |
high voltage load switch |
42/48 |
| (kV/lmin) |
high voltage side |
35 |
| |
low voltage side |
2.5 |
5 |
thunder impact compression resistance£¨kV£© |
75 |
6 |
rated short time tolerant current£¨kA/2s£© |
16 |
7 |
max. fusing current of in support protection fuse£¨kA£© |
50 |
8 |
tapping scope of non-load regulating tapping switch
|
¡À5%(¡À2*2.5%) |
9 |
allowable rising temperature£¨K£© |
65 |
10 |
level of noise£¨dB£© |
¡Ü50 |
|
| |
| ZBW combined transformer
substation: |
 |
|
| characteristics of
structure: |
1. The main structure adopted cold pricking board with special treatment
or double deck airproof structure of materials of aluminum & zinc-sprending
board of anti-corrosive capability, or nonmetal materials, simulated
indoors operation environment, provided guarantee for the liable operation
of the first and second system, and this structure makes the transformer
realize dampproof, dustproof and dewproof capabilities;
2. adapted both in cable turnover wire and turnover wire built on
stilts;
3. The transformer body adopted Mu or Pin layout method of three rooms:
high voltage room, transformer room, and low voltage room with compact
structure to save space in maximum; among the rooms of the transformer
substation there are small seperate rooms insulated by insulating
board;
4. The accessory of high voltage mainly adopted versatility air compression
load switch, vacuum load switch, SF6 load switch, plus structure of
fuse combination electric appliances as the main switch protecting
transformer;
5. The low voltage room is able to adopt screen-type, drawing out
type, faceplate type, standard switch tank or adopted non-standard
structure according to customers' requirements; compensate according
to 10-20% of volume of the transformer or according to customers'
requirements;
6. Generally the transformer chooses oil-immersing low loss electric
power transformer or epoxy dry transformer. According to customers'
requirements;
7. Adopted two methods: national aeration and forced aeration to make
the aeration and cooling perfect. The fan has temperature control
device, automatically starting and closing according to the set temperature
to make sure of fully load operation of transformer. |
| parameters of technical
capability: |
sequence number |
name |
unit |
high voltage side |
low voltage side |
transformer |
1 |
rated frequency |
Hz |
50 |
50 |
50 |
2 |
rated voltage |
KV |
10 |
0.4 |
10/0.4 |
3 |
rated volume |
KVA |
|
|
50-1250 |
4 |
rated current |
A |
400-630 |
100-2000 |
|
5 |
rated short opening current |
KA |
31.5 |
|
|
6 |
rated short closing current |
KA |
50 |
|
|
7 |
rated stable current |
KA |
50 |
|
|
8 |
lmin working frequency compression resistance |
KV |
to ground42£»fracture48 |
2.5 |
|
9 |
thunder impact compression resistance |
KV |
to ground75£»fracture85 |
|
75 |
10 |
protection grade of transformer shell |
|
IP43 |
11 |
level of noise |
dB |
55£¨oil£©/65£¨dry£© |
|
| |
 |
| cable branch transformer: |
| characteristics
of functions: |
outdoors whole insulated, whole airproof, free of maintenance;
dustproof, dampproof, preventing flood, antisepsis;
agile combination, methods of connection can reach 8
circuits; able to connect with short fault indicator
and quikly find out the fault of circuitry; |
small dimension, compact structure, convenient to be
installed; save cable, reduce wire loss, improve the
liability of supplying power; painting green according
to Munse 6G standard with beautiful surface; according
with ANSI C57.12.28 standard. |
|
|
| parameters of technical capability: |
specifications |
200A£¨branch net£© |
600A(branch net) |
| rated voltage |
15kV |
15kV |
| rated current |
200A |
600A |
| rated short time tolerant current |
16kA |
40kA |
| 1 minute working frequency compression resistance |
42kV |
42kV |
| 15 minutes direct current compression resistance |
53kV |
78kV |
| thunder impact compression resistance£¨BIL£© |
95kV |
125kV |
| min. corona starting voltage |
11kV |
19kV |
|
|