¡¡10KV distribution transformer
Technical parameters of 9model 6, 10kv double-winding non-excitation regulating distribution transformer:
type
voltage combination
connection group number
loss KW
air
load current %
short impedance %
weight kg
outside
limited
size mm
rail distance mm
high voltage KV
high voltage tapping scope
low voltage KV
air load
load
machine body
oil
oil tank
total weight
S9-5
6
6.3
10
¡À5%
0.4
YynO
0.05
0.165
4
4
80
45
55
145
845*360*882
350
S9-10
0.07
0.20
3
105
50
60
180
860*400*940
350
S9-20
0.10
0.45
2.3
150
65
65
250
955*460*970
400
S9-30
0.13
0.60
2.1
185
75
75
305
985*650*1015
400
S9-50
0.17
0.87
2.0
245
95
95
400
1030*710*1060
400
S9-63
0.20
1.04
1.9
290
105
105
470
1130*755*1220
550
S9-80
0.25
1.25
1.8
325
115
115
520
1070*775*1145
550
S9-100
0.29
1.50
1.6
375
130
140
600
1160*790*1275
550
S9-125
0.34
1.80
1.5
415
140
160
675
1190*790*1285
550
S9-160
0.40
2.20
1.4
490
160
185
780
1250*820*1345
550
S9-200
0.48
2.60
1.3
585
180
195
925
1450*830*1385
550
S9-250
0.56
3.05
1.2
675
200
230
1050
1500*850*1450
660
S9-315
0.67
3.65
1.1
815
235
285
1265
1610*1015*1485
660
S9-400
0.80
4.30
1.0
4.5
990
285
325
1545
1435*1025*1555
660
S9-500
0.96
5.10
1.0
1160
320
380
1790
1475*1040*1605
660
S9-630
1.20
6.20
0.9
1435
425
475
2260
1810*1230*1750
820
S9-800
1.40
7.50
0.8
1670
490
540
2610
1875*1260*1860
820
S9-1000
1.70
10.30
0.7
1820
500
580
2850
1900*1480*1885
820
S9-1250
1.95
12.00
0.6
2220
600
750
3450
2030*1450*1930
820
S9-1600
2.40
14.50
0.6
2665
720
875
4130
2095*1660*1970
820
 
¡¡35KV transformer
"Technical parameters of 9model 35kv double-winding non-excitation regulating distribution transformer:
type
voltage combination
connection group number
loss KW
air load current %
short impedance %
weight kg
rail distance mm
high voltage KV
high voltage tapping scope
low voltage KV
air load
load
machine body
oil
oil tank & accessories
total weight
S9-50
3.5
¡À5%
0.4
YynO
0.21
1.22

2.0

6.5
268
326
235
825
550
S9-100
0.29
2.03

1.8

365
365
285
1020
660
S9-160
0.37
2.83
1.65
520
456
325
1290
660
S9-200
0.44
3.33
1.55
630
490
345
1456
660
S9-250
0.51
3.96
1.4
720
545
410
1675
660
S9-315
0.61
4.77
1.4
855
665
435
1880
660
S9-400
0.73
5.76
1.3
1015
745
505
2155
820
S9-500
0.86
6.93
1.3
1175
865
580
2410
820
S9-630
1.04
8.28
1.25
1585
765
665
2840
820
S9-800
1.23
9.9
1.05
1775
1040
890
3685
820
S9-1000
1.44
12.15
1.0
2065
1165
955
4185
820
S9-1250
1.76
14.67
0.85
2336
1255
1218
4960
1070
S9-1600
1.12
17.55
0.75
2845
1380
1235
5464
1070
Technical parameters of 9model 35kV double-winding load regulating transformer
type
voltage combination
connection group number
loss KW
air load current %
short impedance %
weight kg
rail distance mm
high voltage KV
high voltage tapping scope
low voltage KV
air load
load
machine body
oil
oil tank & accessories
total weight
SZ9-2000

3.5

38.5

¡À3%*

2.5%

6.3
10.5
Yd11
3.21
22.50
1.00
6.5
3040
1775
1630
5905
1070
SZ9-2500
3.82
24.15
1.00
3530
1945
1900
6950
1070
SZ9-3150
4.55
28.90
0.90
7.0
3770
2102
2160
7967
1070
SZ9-4000
5.50
34.10
0.90
4500
2400
2815
9720
1070
SZ9-5000
6.50
40.00
0.85
6015
2660
2900
10625
1070
SZ9-6300
7.80
43.00
0.85
7.5
6556
3060
3456
13075
1070
S£¨F£©Z9-8000
6.3
6.6
10.5
11
YNd11
11.00
47.50
0.75
8066
3330
3986
15300
1475
S£¨F£©Z9-10000
13.00
56.20
0.75
9705
3750
5205
17858
1475
S£¨F£©Z9-12500
15.30
66.50
0.70
8.0
10963
4215
5675
20042
1475
S£¨F£©Z9-16000
15.20
74.00
0.68
13140
4900
6020
27390
2040
S£¨F£©Z9-20000
18.36
86.00
0.60
17160
7340
5250
29750
2040
S£¨F£©Z9-25000
23.00
1000.0
0.50
22550
9330
6080
41000
2040
S£¨F£©Z9-31500
26.77
126.0
0.40
27000
9990
7215
46000
2040
 
 
 
 
ADD:East End,Zhengyang Road,Chengyang District,QingDao
Tel:(86 532)7731888 7731645 ¡¡Fax:(86 532)7731139 ¡¡Email:Sales@qdhuadong.com